Home/Case studies/Ninety faults found on a five megawatt solar farm in one survey

Ninety faults found on a five megawatt solar farm in one survey

A five megawatt solar farm flown with a thermal imager in one visit. The survey found ninety faults, including four string faults that between them had taken eighty eight panels off power.

Thermography · fault map
Plan of the solar farm with each panel row drawn, and the faults found marked in red
FlyThru fault map diagram
90

faults found in a single survey

The problem

A solar farm only earns while its panels are generating. A panel that has stopped, or a string that has dropped out, looks the same as a working one from the ground. The loss shows up weeks later in the generation figures.

This was a typical five megawatt site, surveyed in the summer of 2017 to find out which parts of it were not working.

What was flown

An aircraft was flown up and down the array carrying a thermal imager. A faulty panel runs hotter than the ones either side of it, so it shows as a bright patch in the thermal image even where nothing is visible in daylight.

The whole site was covered in one visit.

What came back

A fault map of the whole site, with every row drawn and every fault marked, so the site manager could walk straight to each one. The thermal image of each fault sits behind it.

A FlyThru engineer analysed the data and produced a full site maintenance report. Faults are reported by type, because the type determines who needs to attend: a single hotspot, multiple hotspots, a heated substring or diode fault, vegetation covering a panel, a string fault, an inverter fault, patchwork, and shading from trees or power lines.

Four of those eight types were found here: string faults, vegetation covering panels, hotspots and heated substrings.

Ninety faults were found in the one survey. Four of them were string faults, and between them those four had taken eighty eight panels off power. Working from the fault map, the site manager traced the electrical connection faults behind them and returned the panels to generating.